File Download

There are no files associated with this item.

  • Find it @ UNIST can give you direct access to the published full text of this article. (UNISTARs only)
Related Researcher

정지훈

Jung, Jee-Hoon
Advanced Power Interface & Power Electronics Lab.
Read More

Views & Downloads

Detailed Information

Cited time in webofscience Cited time in scopus
Metadata Downloads

Test-bed implementation of DC microgrid in islanding mode

Author(s)
Jeong, Dong-KeunBaek, Ju-WonCho, Jin-TaeKim, Hee-JeJung, Jee-Hoon
Issued Date
2015-06-04
DOI
10.1109/ICPE.2015.7168012
URI
https://scholarworks.unist.ac.kr/handle/201301/35529
Fulltext
http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=7168012&tag=1
Citation
IEEE ICPE-ECCE Asia, pp.1736 - 1741
Abstract
In order to increase the reliability and response speed of a DC microgrid system, the power management algorithm for autonomous operation is proposed using a DC-bus signaling (DBS) method, instead of the centralized power management system which needs communications among power interfaces. The DC-bus voltage is considered as an information signal of the status of the DC-bus. In addition, DC-bus voltage bands are proposed to classify the scenarios of DC-bus conditions. The DC microgrid components individually operate to achieve the functionality of the system control in the DC-bus voltage band. This paper suggests a control strategy for the power management among independent components in the islanding mode. Its test-bed contains the power management algorithm which consists of a grid-connected AC/DC rectifier, a bidirectional DC/DC converter, a renewable energy simulator, DC loads, and a DC-bus protector. The proposed power management algorithm in the islanding mode is analyzed via simulation result, which is verified from the proposed DC microgrid test-bed.
Publisher
IEEE

qrcode

Items in Repository are protected by copyright, with all rights reserved, unless otherwise indicated.